Research on the Key Parameters and Device Capacity Decoupling Analysis of Full Bridge MMC DC Ice-Melting Device [PDF]
[Introduction] This article aims to study the issue of the melting capacity and reactive output capacity of the full bridge modular multi-level converter (MMC) type DC (Direct Current) melting ice device under different operating modes.
Rui HE, Xiaogang WU
core +1 more source
Modal Parameter Identification of Low Frequency Oscillation in Power System Based on Ambient Data [PDF]
Low frequency oscillation is one of the key problem affecting the safe and stable operation of interconnected power system, variational modal decomposition (VMD) was used to extract low-frequency oscillation signals from ambient data, and a method of low-
GAO Yanfeng, HWANG Jin Kwon, YAN Hongyan
core +1 more source
大容量试验是检验电力装备性能,保障装备安全可靠运行的重要环节。现有的大容量试验回路主要依靠人工操作,存在流程复杂、效率低且易出错的问题。针对大容量试验回路智能化控制的难题,研究建立了冲击发电机单电机短路模型和双电机并联短路模型,分析了发电机短路特性,结合典型大容量试验回路设计了一键顺控方案,提出试验回路一键顺控操作流程。通过对发电机短路模型和大容量试验回路系统的仿真 ...
吴益飞 +7 more
core +1 more source
架空线柔性直流电网是实现大规模可再生能源广域协调互补和可靠送出的有效解决方案,是未来高压大容量柔性直流输电的重要应用方向。直流线路短路电流是柔性直流电网中换流阀、直流断路器及电抗器等关键主设备参数选取的重要依据之一。通过建立双极柔性直流电网单个换流站在直流线路不同短路故障类型下的等效电路数学模型,构建了故障时刻双极柔性直流电网等效电路网络模型,提出了一种适用于双极柔性直流电网的单极接地、单极接中性线及双极短路的暂态短路电流定量分析方法,实现了双极柔性直流电网直流线路任意故障类型 ...
裴翔羽 +5 more
doaj +1 more source
分析直流偏磁对变压器造成的异常振动噪音规律是预防变压器故障的前提。为此,针对E型电力变压器,根据"铁心—绕组"模型分析了直流偏磁下变压器的振动噪音机理并利用Comsol搭建了电磁—振动—声场多物理场耦合模型,研究直流量大小、直流量从初级绕组流入和直流量从次级绕组流入两种情况下,直流偏磁对不同运行状况变压器的振动噪音规律和对绕组电压电流波形的影响。研究表明:直流量从初级绕组流入对空载变压器的影响最大,随直流量的增加铁心绕组上的振动噪音加剧且振动噪音最大值分布在铁心上 ...
吴静 +6 more
doaj
Capacitor Voltage Ripple and Harmonics Analysis in MMC [PDF]
[Introduction] The rapid development of VSC-HVDC provides practical support for MMC (Modular Multi-Level Converter) topology. Takes a half bridge MMC converter as an example, the relationship between steady-state capacitor voltage fluctuation, harmonic ...
Gang LI +4 more
core +1 more source
文中以500 kV张北柔直输电线路工程为研究对象,构建5因素3水平的L16(35)正交试验方案,利用PSCAD/EMTDC软件搭建感应电压与电流的仿真模型,分析了导线排列方式、交直流回路间垂直距离、直流极导线间水平间距、回流线等导线布置方案对带电回路在停运检修线路上感应电压与电流的多因素相互影响程度及规律。结果表明:交直流线路采用上下两层均平行布置时,各感应分量最小,且两极线间感应分量差值亦最小;回流线可降低检修线路上感应电压与电流约35%;影响静电耦合分量因素的因子主次顺序为:垂直间距、运行电压 ...
吴田 +4 more
doaj
Improved sub-band JND model with textural decomposition and its application in perceptual image coding [PDF]
In order to improve the accuracy of the just noticeable difference (JND) model in transform domain, an en-hanced JND model with a new method for contrast masking factor estimation was proposed. The image was decomposed and the textural image was used for
Cheng-dong LAN +4 more
core +1 more source
作为直流输电系统最重要的设备之一,换流变压器的绝缘状态对直流输电系统的安全稳定运行起着至关重要的作用。其阀侧绕组不同位置需要承受不同交直流分量比例的复合电压。而现有研究主要针对1:1复合电压比例,其他电压比例研究较少。文中基于脉冲电流法与恒定电压法,建立了复合电压下油纸绝缘局放实验平台,研究了1:1、1:3、1:5和1:7交直流比例复合电压下针板电极有油隙模型、针板电极沿面强/弱垂直分量模型的局放起始放电电压、谱图特性和放电典型特征。结果表明:沿面强垂直分量模型的起始放电电压明显低于弱垂直分量模型 ...
张永武 +6 more
doaj
柔性直流并入城市电网后对换流站近区短路电流的影响研究 [PDF]
大型城市供电电网短路电流已经接近断路器遮断容量,柔性直流接入系统后,会在故障期间提供工作电流,导致交流系统短路电流超标,柔性直流输送功率受限。从柔性直流内外环控制方式及交流系统短路电流计算原理出发,分析得出柔性直流短路电流的幅值和相位对并网点的短路电流影响均较大,其中幅值受外环电流限幅环节的影响易于控制,因此需着重对相位进行控制。基于此提出了一种降低柔性直流输电换流站两端PCC点短路电流的控制策略。以厦门柔性直流工程为例,开发了交直流混合模型,与实测波形对比验证了模型的正确性。通过对不同类型故障下 ...
寇龙泽, 朱琳, 范征, 谷怀广
core +1 more source