分析了河南省2起220kV输电线路复合绝缘子芯棒断裂掉串的原因。断串均发生在绝缘子的高压端,端口垂直于芯棒轴线,断口大部分光滑平整;产品采用内锲式连接工艺、室温硫化硅橡胶封堵和普通芯棒;发生断串的档距都接近700 m,属于大档距。结合拉力抽检实验,提出220kV以上输电线路,应采用压接式复合绝缘子,其端部采用高温硫化硅橡胶、多层密封工艺,采用耐酸芯棒;对于大跨越线路段,全部采用双悬垂串、"V"形串或"八"字形串绝缘子,并尽可能采用双独立挂点。
卢明, 马晓久, 阎东, 李刚
doaj
[A review of brain-like spiking neural network and its neuromorphic chip research]. [PDF]
Zhang H, Xu G, Guo J, Guo L.
europepmc +1 more source
Snow sculpture — possibility and prospect — [PDF]
PDFdepartmental bulletin ...
317 +4 more
core
介绍了在芯棒中植入光纤光栅的复合绝缘子,并通过光纤光栅来在线监测复合绝缘子芯棒应力的变化,从而用于实时监测复合绝缘子的运行状态。先后对光纤光栅复合绝缘子进行了实验室应力测量试验和110 kV输电线路挂网试验,试验结果表明:光传感器能用于复合绝缘子芯棒应力的测量,可实时监测复合绝缘子的运行状态。
曹敏 +4 more
doaj
[Clinical application of percutaneous pedicle screw placement guided by ultrasound volume navigation combined with X-ray fluoroscopy: a prospective randomized controlled study]. [PDF]
Lin X +5 more
europepmc +1 more source
为研究分析河南电网某500 kV重要输电线路复合绝缘子断裂的原因,对断裂复合绝缘子及故障处相邻铁塔上挂网运行的6支复合绝缘子,依照GB/T 19519-2014和DL/T 864-2004进行了机械特性试验、耐应力腐蚀试验和憎水性试验,同时对芯棒进行了材质分析,并对断裂的整支绝缘子进行了解剖分析。试验结果表明,6支绝缘子机械破坏负荷值在0.91 SML以上,憎水性为HC4HC5级,故障绝缘子试品耐应力腐蚀试验4小时发生断裂,芯棒玻璃纤维硼(B)元素含量为5.8 ...
邵颖彪 +5 more
doaj
复合绝缘子所采用的纤维浸渍树脂拉挤成型芯棒 ,其材质构成的波动 ,将较大地影响产品压接连接界面结构组装时芯棒弹性变形的性能参数 ,应适当调整修正 ...