The Influence of VDCOL Parameters on the Recovery Characteristic after Commutation Failures of HVDC Links Fed into Weak AC Systems

2022 4th International Conference on Power and Energy Technology (ICPET), 2022
The faults occurred in the receiving terminal AC system of an HVDC transmission link may cause commutation failures of the inverters. When the receiving AC system is weak, the AC/DC system may be difficult to restore to a stable operation state due to ...
Jiale Hong, L. Qin
exaly   +3 more sources

Research on HVDC system parameter domain based on VDCOL dynamic characteristic optimization

2024 4th International Conference on Electrical Engineering and Control Science (IC2ECS)
During commutation failure(CF), the transient reactive power characteristics of the HVDC system are closely related to the Voltage Dependent Current Order Limiter (VDCOL) control parameters.
Tian-Shu Wang   +3 more
exaly   +3 more sources

Mitigating Commutation Failures in High-Voltage DC Transmission Systems with a Logistic Function-Based AC/DC-VDCOL Switchover Control

2023 International Conference on Power System Technology (PowerCon), 2023
This research aims to enhance the stability and reliability of high-voltage DC transmission systems. An analysis of the control effects of two input methods (AC voltage and DC voltage) in the VDCOL module was conducted, and an improved logistic function ...
Shuqing Zhang, Xianfa Hu, Shaopu Tang
exaly   +3 more sources

A VDCOL Improvement Strategy for CLCC with Improved Inputs

2024 The 9th International Conference on Power and Renewable Energy (ICPRE)
The high voltage direct current (HVDC) transmission technology based on controllable line commutated converter (CLCC) avoids the problem of conventional DC phase commutation failure and provides a brand new way for HVDC transmission to the grid.
Dezhen ZHANG, Danzhen Gu, Xuejun Xiong
exaly   +3 more sources

Bus voltage cooperative control strategy of AC/DC system based on VDCOL link and fuzzy controller

2024 4th International Conference on Smart Grid and Energy Internet (SGEI)
In order to suppress the transient overvoltage at the bus terminal of AC/DC system, a transient overvoltage coordination control strategy based on improved VDCOL curve and fuzzy control algorithm is proposed.
Minglei Jiang
exaly   +3 more sources

An Improved VDCOL Control Strategy for Mitigating Continuous Commutation Failure in HVDC Transmission

2021 IEEE Sustainable Power and Energy Conference (iSPEC), 2021
To suppress the continuous commutation failure (CCF) and improve fault resilience of high voltage direct current (HVDC) due to alternative current (AC) fault occurred in inverter side, an improved voltage dependent current order limiter (VDCOL) control ...
Zhi-Chao Yang   +5 more
semanticscholar   +2 more sources

Energy Variation Rate-Based Transient Stability Analysis Method for VDCOL Control of HVDC Transmission System

2022 IEEE Sustainable Power and Energy Conference (iSPEC), 2022
During the recovery process of commutation failure, the current command repeatedly enters and exits the voltage dependent current order limiter (VDCOL) control because of the interaction between the DC regulation speed and the AC voltage recovery rate ...
Ze-Yu Cao   +5 more
semanticscholar   +2 more sources

VDCOL Coordinated Control Strategy for Successive Commutation Failure Mitigation in Multi-infeed HVDC Systems

2021 IEEE Power & Energy Society General Meeting (PESGM), 2021
Control strategy improvement is an effective method for commutation failure mitigation in line-commutated-converter-based high voltage direct current (LCC-HVDC).
Chen-Yi Zheng, Yi Tang, Qi Wang
semanticscholar   +2 more sources

Commutation Failure Mitigation in LCC-HVDC Systems Through Improvement of VDCOL Characteristic

2025 IEEE 7th International Conference on Energy, Power and Grid (ICEPG)
Commutation failure (CF) is a common issue encountered on the inverter side of line-commutated converter high voltage dc (LCC-HVDC) systems. The primary cause is a fault on the AC side of the inverter, which leads to the unexpected re-conduction of the ...
Jiahui Li, Xiaohui Liu, Meng Li, Jia Yu
semanticscholar   +2 more sources

Design of Adaptive Improved VDCOL Control Strategy for Suppressing Subsequent Commutation Failure in HVDC Transmission Systems

2025 2nd international conference on DC technologies and systems (DCTS)
The VDCOL control in the High-Voltage Direct Current (HVDC) transmission system can limit the DC current after a fault, thereby reducing the likelihood of subsequent commutation failures in the system.