在中性点经消弧线圈接地方式的配电网发生单相接地故障时,对接地故障的处理、故障电流的控制、故障点的绝缘恢复、故障线路的查找等方面进行了分析,讨论了故障点对人身安全的影响;讨论了由于故障导致接地选线难的因素;讨论了故障发生后残流控制与故障恢复、弧光过电压及中性点位移电压的关系;讨论了配电网与消弧线圈接地方式在发展中存在的矛盾,认为目前该接地方式存在有严重的安全瓶颈、选线瓶颈与容量瓶颈,存在消弧困难和弧光接地过电压的问题,提出了中性点动态接地改造的重要性,并对其原理进行阐述。
张辉
doaj
不同接地方式下变压器35 kV绕组外部过电压特性分析及防治措施
变压器35 kV绕组中性点接地方式较多,现有设计没有对不同接地方式下变压器的防雷措施进行专门考虑,导致变压器35 kV侧雷击事故频发。为了对不同接地方式下变压器35 kV绕组雷电侵入波特性及防治措施进行研究,采用电磁暂态分析软件ATP-EMTP建立仿真模型,对35 kV绕组星形接线的配网变压器和三角形接线的风电场升压变进行了雷电侵入波电磁暂态仿真,分析了导致35 kV绕组绝缘损坏的雷电侵入波特点,考察了不同安装方式下避雷器对雷电侵入波防治的有效性。研究表明不同接地方式下变压器35 ...
胡晓宇, 陈皓, 刘守豹
doaj
ABSTRACT Objectives Our aim was to examine the prenatal profiles of pregnancies affected by an atypical chromosomal aberration, focusing on pathogenic copy‐number variants (pCNVs). We also wanted to quantify the performance of combined first‐trimester screening (cFTS) and a second‐trimester anomaly scan in detecting these aberrations. Finally, we aimed
K. Gadsbøll +6 more
wiley +1 more source
20 kV电压等级配电设备的选择与系统中性点接地方式密切相关。20 kV中压配电网的不同中性点接地方式各具有其特点及适用范围,在此基础上,通过相关标准和实际运行经验对不同中性点接地方式下相关设备的性能参数进行分析与比对,以设备绝缘水平和经济性能作为综合指标对20 kV电压等级配电设备的选择进行了探讨,在现行的国标和行标等对设备性能参数规定较少的情况下,为20 kV电压等级建设提供借鉴。
杨德伦, 李景禄, 张萌, 彭利强
doaj
Potholes, 311 reports, and a theory of heterogeneous resident demand for city services
Abstract Understanding the needs of residents is vital in public administration and management, as this helps officials when making choices on policies and service distribution. Increasingly, cities rely on 311 systems to elicit information from residents on emergent needs in particular policy areas (e.g., road quality, pest control).
Scott J. Cook +2 more
wiley +1 more source
针对目前西安电网中变压器中性点接地方式存在的安全隐患,提出了330 kV自耦变压器和110 kV变压器都经过小电抗接地的优化方式。仿真计算表明,经过适当的小电抗接地后,330 kV自耦变110 kV侧母线上的单相短路电流明显减小,其他110 kV变压器中性点过电压显著减小,保证了中性点绝缘不受威胁和系统运行的安全性。
王育路 +4 more
doaj
Abstract The availability of hospital‐based dental services across Australia varies with a number of hospitals disestablishing dental departments due to rising costs. However, the perceived costs are difficult to quantify as funding models used to capture activity are not uniform across health facilities.
Pritam Daniel Sundaresan +3 more
wiley +1 more source
35 kV系统中铁磁谐振过电压频繁发生,对系统造成很大的危害。利用理论分析和EMTP-RV仿真相结合的方法,分析了中国35 kV系统3种中性点接地方式(中性点不接地、经消弧线圈或小电阻接地)下由电磁式电压互感器(PT)饱和引起的铁磁谐振过电压,研究结果表明,在中性点经消弧线圈或小电阻接地系统中,只要消弧线圈或小电阻的参数选取合适,能够将中性点位移电压限制在电压三角形内,可有效抑制铁磁谐振的发生。
汪伟 +6 more
doaj
通过漏电电流暂态、稳态、人身触电安全、串联谐振过电压等方面的研究,对3-3 kV电网中性点经电阻接地方式进行了全面的分析,并对故障暂态过程进行仿真,给出了有关的技术参数,提出了中性点电阻值的取值范围,为中性点经电阻接地运行方式的设计和应用提供了理论依据。